Wet-Well Cycle Time Calculator – Lift Station Pumps

Wet-Well Cycle Time Calculator

Lift-station pump cycling — fill time, pump-down time, starts per hour and run percent at minimum, average and peak inflow.











Scenario Fill (min) Pump-down (min) Cycle (min) Starts/hr Run % Verdict
Min
Avg
Peak

Formulas
Working volume (gal) = area (ft²) × (ON level − OFF level, ft) × 7.48
Fill time (min) = working volume ÷ inflow (gpm)
Pump-down time (min) = working volume ÷ (pump rate − inflow)
Cycle time = fill + pump-down · starts/hour = 60 ÷ cycle · run % = pump-down ÷ cycle × 100
For educational and preliminary-design purposes. Confirm pump cycling limits with the pump and motor manufacturer.

← All water treatment calculators