Minimum Self-Cleansing Slope Calculator

Minimum Self-Cleansing Slope Calculator

What grade does this sewer need to hit self-cleansing velocity? Enter the diameter and target velocity to get the minimum slope from Manning’s equation.




Minimum Slope
Item Value

How the calculation works

Manning’s equation rearranged for slope (full flow, US units)
V = (1.486 / n) × R2/3 × S1/2
S = [ V × n / (1.486 × R2/3) ]2
R = D / 4 for a circular pipe flowing full
Slope in percent = S (ft/ft) × 100
Diameter (in) Min slope at 2 ft/s, n = 0.013 (ft/ft)
8 0.0033
10 0.0025
12 0.0019
15 0.0014
18 0.0011
24 0.0008

Notes & limitations

The 2 ft/s self-cleansing velocity at design flow is the long-standing Ten State Standards (GLUMRB) criterion for sanitary sewers; the slope formula is Manning’s equation solved for S with R = D/4. The reference slopes above are the exact Manning solutions for the listed inputs — try them in the tool to confirm.
  • This is the slope for the target velocity at full flow. At partial depths the velocity differs — the full-flow check is the standard design simplification.
  • Flatter grades than the computed minimum need justification (and usually more frequent cleaning); steeper is fine but watch maximum velocity and drop structures.
  • Use the design n, not the new-pipe n — aged sewers run rougher, which demands a steeper slope for the same velocity.
  • Minimum diameter and minimum slope rules vary by state — confirm against the applicable standards before finalizing plans.