Hydropneumatic Tank Drawdown Calculator

Hydropneumatic Tank Drawdown Calculator

Drawdown is the water a pressure tank actually delivers between pump cut-out and cut-in. Enter your tank and switch settings to size it with Boyle’s law.






Tank Drawdown
Item Value

How the calculation works

Boyle’s law on the air cushion (absolute pressures, psia = psig + 14.7)
P0 = precharge, P1 = cut-in, P2 = cut-out (all absolute)
Drawdown Vd = Vtank × P0 × (1/P1 − 1/P2)
When precharge equals cut-in (P0 = P1), this simplifies to Vd = Vtank × (1 − P1/P2)
Drawdown time ≈ drawdown (gal) ÷ pump flow (gpm)
Common switch setting Cut-in / cut-out (psig) Typical drawdown (% of tank)
20/40 20 / 40 ~30%
30/50 30 / 50 ~27%
40/60 40 / 60 ~25%

Notes & limitations

Boyle’s law (P1V1 = P2V2 at constant temperature) is the standard basis for hydropneumatic tank drawdown sizing (AWWA M22; tank manufacturer engineering data).
  • Pressures must be absolute in the formula — this tool adds 14.7 psi for you. Never mix gauge and absolute pressures.
  • Set precharge with the tank drained of water, about 2 psi below cut-in. Precharge above cut-in wastes usable drawdown; precharge far below cut-in risks the bladder/diaphragm over-extending.
  • Drawdown controls pump cycling: short drawdown (or a waterlogged tank with lost air) causes rapid cycling and motor wear. Size tanks for an acceptable minimum pump run time per the motor manufacturer’s starts-per-hour limit.
  • Bladder/diaphragm and plain steel (air-over-water) tanks follow the same Boyle’s-law math, but air-over-water tanks lose air over time and need an air-volume control.

← All water treatment calculators · Related: Water Age & Tank Turnover Calculator