Hydropneumatic Tank Drawdown Calculator
Drawdown is the water a pressure tank actually delivers between pump cut-out and cut-in. Enter your tank and switch settings to size it with Boyle’s law.
Tank Drawdown
| Item | Value |
|---|
How the calculation works
Boyle’s law on the air cushion (absolute pressures, psia = psig + 14.7)
P0 = precharge, P1 = cut-in, P2 = cut-out (all absolute)
Drawdown Vd = Vtank × P0 × (1/P1 − 1/P2)
When precharge equals cut-in (P0 = P1), this simplifies to Vd = Vtank × (1 − P1/P2)
Drawdown time ≈ drawdown (gal) ÷ pump flow (gpm)
P0 = precharge, P1 = cut-in, P2 = cut-out (all absolute)
Drawdown Vd = Vtank × P0 × (1/P1 − 1/P2)
When precharge equals cut-in (P0 = P1), this simplifies to Vd = Vtank × (1 − P1/P2)
Drawdown time ≈ drawdown (gal) ÷ pump flow (gpm)
| Common switch setting | Cut-in / cut-out (psig) | Typical drawdown (% of tank) |
|---|---|---|
| 20/40 | 20 / 40 | ~30% |
| 30/50 | 30 / 50 | ~27% |
| 40/60 | 40 / 60 | ~25% |
Notes & limitations
Boyle’s law (P1V1 = P2V2 at constant temperature) is the standard basis for hydropneumatic tank drawdown sizing (AWWA M22; tank manufacturer engineering data).
- Pressures must be absolute in the formula — this tool adds 14.7 psi for you. Never mix gauge and absolute pressures.
- Set precharge with the tank drained of water, about 2 psi below cut-in. Precharge above cut-in wastes usable drawdown; precharge far below cut-in risks the bladder/diaphragm over-extending.
- Drawdown controls pump cycling: short drawdown (or a waterlogged tank with lost air) causes rapid cycling and motor wear. Size tanks for an acceptable minimum pump run time per the motor manufacturer’s starts-per-hour limit.
- Bladder/diaphragm and plain steel (air-over-water) tanks follow the same Boyle’s-law math, but air-over-water tanks lose air over time and need an air-volume control.
← All water treatment calculators · Related: Water Age & Tank Turnover Calculator